Two-Pole Tester (voltage indicator)

In short

A two-pole tester, a voltage indicator, is the instrument safe isolation is done with. It has two probes and a ladder of lights (LEDs).

If this is your home: this page is written for heating engineers. Mains wiring and gas appliances are not DIY jobs; call a Gas Safe registered engineer. If you smell gas, leave the building and call the National Gas Emergency Service on 0800 111 999.

What it is

A TWO-POLE TESTER, a voltage indicator, is the instrument SAFE ISOLATION is done with. It has two probes and a ladder of lights (LEDs). It has no ranges to set, and it does not read resistance.

The method:

  • Prove it on the proving unit.
  • Test every conductor against every other.
  • Read dead on all of them.
  • Prove it again.

A reading on a live circuit proves it too.

What the meter reads

230 volts (230 V): every light (LED) is lit. Dead: none.

DC as well, either way round: direct current (DC), as on an OpenTherm pair. With nothing on the pair, about 24 V DC, it lights the 12 and 24 V LEDs.

The PROVED lamp means the TESTER works, never that the circuit is dead. It is this simulator's own: a tester on site simply lights on a known live.

It lights on the proving unit, or on a live circuit of 50 V or more. It goes out on a dead reading. So after the dead test, prove the tester again.