Heating on but no hot water: how an engineer approaches it
In short
When the heating works but the hot water does not, the working zone has already proved the supply, the boiler and the pump. The fault is on the hot water path: the programmer’s hot water output, the cylinder thermostat, the hot water valve and the wires between them. See it, then trace that path with a meter.
If this is your home: this page is written for heating engineers, and for learners under the supervision of one. It explains how the wiring works; it is not training to do the work. In England and Wales, electrical work in a home must meet the Building Regulations (Part P), and some of it must be notified to building control or done by a registered electrician; Scotland and Northern Ireland have their own rules. For the wiring, call a registered electrician or a heating engineer competent in controls. Work inside a gas boiler is for a Gas Safe registered engineer only. If you smell gas, leave the building and call the gas emergency number: 0800 111 999 in Great Britain, 0800 002 001 in Northern Ireland.
Live tests. On site, any reading taken with the supply on is work on or near live parts. Regulation 14 of the Electricity at Work Regulations 1989 allows it only when working dead is unreasonable, as when a fault shows only while the controls work, and only with suitable precautions: test leads made to the HSE’s guidance note GS38, fingers behind the guards. Regulation 16 allows it only for a competent person, or a learner under the supervision of one. Wiring and repairs are always done dead. In the simulator, nothing is live.
What the customer says
“Heating’s lovely and warm but there’s no hot water. The cylinder’s cold.”
That is a good start. It tells you which zone to look at and that the other one works. It is not a diagnosis. Ask a few short questions before you open anything. Since when? Has anyone changed a setting, fitted a new control or had other work done? Is the hot water set to come on at this time of day?
This page is about a system with a hot water CYLINDER, wired with a programmer, a cylinder thermostat and a motorised valve. A combi boiler makes hot water inside itself, with no wiring from the controls. On a combi, heating but no hot water points inside the boiler, and that is a job for a Gas Safe registered engineer.
See the fault for yourself
Before you touch anything, see it happen. Ask for the hot water on its own: hot water on at the programmer, heating off. Then watch the hot water zone with nothing else running.
Look at the simple things first:
- Is the programmer’s hot water channel actually on, or is it waiting for its next time, on holiday or switched off?
- Is the cylinder thermostat’s dial at a sensible setting?
- Does the hot water valve move? Does the boiler fire?
Many “faults” are settings. Finding that out costs a minute and no parts.
What the working zone already proves
On an S-Plan, the heating zone and the hot water zone share a great deal: the supply, the wiring centre’s supply blocks, the boiler, the pump, and the block where the valves’ orange cores meet the boiler’s switched live.
The heating works. So everything the two zones share works. That narrows the search before you take a single reading.
Write down what works and what does not. On a confusing job, that list is often what finds the fault.
On a Y-Plan the chain is different. Its single valve rests at the hot water port, so for hot water alone the valve does nothing, and the cylinder thermostat’s call fires the boiler itself. The approach below still holds: follow that chain instead.
The hot water path: programmer, cylinder stat, valve
On an S-Plan wired with the common numbering, the hot water DEMAND travels like this:
- The programmer’s hot water ON (HW ON) terminal.
- The wiring centre’s block 6, and on to the cylinder thermostat’s common.
- The cylinder thermostat’s call contact, closed while the water is cool.
- Block 8, and on to the hot water valve’s brown core, which drives its motor.
- Once the valve is fully open, its orange core.
- The block where the orange cores meet, and the boiler’s switched live.
Every link is a wire, a screw or a part. Know the cylinder thermostat’s own map before you test it: which terminal is its common, which is its call. Makers number them differently.
Follow the live to neutral
With the hot water on alone and the cylinder cool, take the readings in the order the demand travels. These are live tests, made only because the fault shows only while the controls work, and only by a competent person or a learner under the supervision of one (regulation 16 of the Electricity at Work Regulations 1989). Set the meter to AC volts (V~). Use test leads made to the HSE’s guidance note GS38: finger guards, metal tips of 4 mm or less, fused leads. Keep the black probe on a neutral: block 2 at the wiring centre, the part’s own neutral at a part.
Each point should read about 230 volts (230 V). The fault lies between the last point with 230 V and the first with 0 V. See last 230 V, first 0 V.
Two traps on this job:
- The block where the orange cores meet is shared. If the heating is calling too, that block reads live from the heating valve. Ask for the hot water alone.
- The cylinder thermostat only calls while the water is cooler than its setting. A cylinder heated by an immersion heater may already be warm enough to stop it calling. Know what state it is in before you read its output.
Prove the part before you condemn it
If the readings stop at a part, do not reach for a new one yet. A valve whose brown reads 230 V to earth but will not move may have no neutral. A thermostat with 230 V in and nothing out may simply be satisfied.
Read across the part’s own live and neutral. Full supply and still nothing happens: then the part has failed. See prove a part with two readings.
Before any repair, isolate the circuit, lock it off and prove it dead, the switched lives included. After the repair, prove it: hot water on alone, the valve opens, the boiler fires, and the cylinder starts to warm. Never leave until you have seen the repair work.
Contains public sector information, some of it published by the Health and Safety Executive, licensed under the Open Government Licence v3.0.
Where it connects
- No hot water: heating fine, cylinder cold
Call-out, by symptom
- Cylinder Thermostat (A)
The part
- S-Plan wiring diagram
Wiring diagram
Read next
- Last 230 V, first 0 V: the rule that finds a fault with three readings
Heating fault finding with a meter: follow the demand point to point, probe to a neutral, and the fault lies between the last 230 V and the first 0 V.
- Prove a part with two readings before you condemn it
A motor needs a live and a neutral. Read live to earth, then live to the part’s own neutral, before you change a valve, a pump or a fuse. Then prove the repair.
- How the wiring centre’s numbered blocks tell the story of an S-Plan
An S-Plan wired in the order it works: the supply on blocks 1 to 3, heating on 4 and 5, hot water on 6 and 8, the valves’ orange cores on 10.