Combi · wiring diagram

Combi boiler with two heating zones wiring diagram

In short

A combi boiler heats the radiators and makes hot water at the tap, so there is no cylinder and no hot water valve. From outside it needs a supply, and a switched live for the heating on its room thermostat terminal: from a room thermostat or a wireless receiver’s switch, or, with two heating zones, from the zone valves’ end switches.

DrawWarm's own combi with two heating zones. Each room stat opens its own 2-port valve; both oranges go to block 10 and on to the combi's LR (HTG) terminal. The wiring centre is fed from the boiler's 230 V OUT: one supply for the boiler and its controls. There is no timer on this canvas: an installation needs one too (Boiler Plus), often the boiler's own plug-in clock.

Combi wired in the DrawWarm simulator

A combi wired in the simulator; this page’s circuit is listed wire by wire below. Wire colours as the lessons teach them. The meter reads what the circuit is doing.

The wiring centre, block by block

A block is a plain conductor: every wire landed on it is joined to every other, and to nothing else. The numbers are the habit the DrawWarm Method teaches, so the next engineer can read your work.

BlockWired here
1Room Thermostat #1 L, DrawWarm Combi OUT_L, 2-Port Valve (heating) G, Room Thermostat #2 L, 2-Port Valve (second heating zone) G
2DrawWarm Combi OUT_N, Room Thermostat #1 N, 2-Port Valve (heating) N, Room Thermostat #2 N, 2-Port Valve (second heating zone) N
3DrawWarm Combi OUT_E, 2-Port Valve (heating) E, 2-Port Valve (second heating zone) E
5Room Thermostat #1 SL, 2-Port Valve (heating) B
9Room Thermostat #2 SL, 2-Port Valve (second heating zone) B
10DrawWarm Combi RT, 2-Port Valve (heating) O, 2-Port Valve (second heating zone) O

Every wire, terminal by terminal

FromTerminalToTerminalColour
DrawWarm CombiOUT_LDrawWarm CombiLR_DHWCopper link
Fused SpurEDrawWarm CombiEGreen/yellow (earth)
Fused SpurNDrawWarm CombiNBlue (neutral)
Fused SpurLDrawWarm CombiLBrown (live)
Room Thermostat #1LWiring Centre1Brown (live)
DrawWarm CombiOUT_LWiring Centre1Brown (live)
DrawWarm CombiOUT_NWiring Centre2Blue (neutral)
DrawWarm CombiOUT_EWiring Centre3Green/yellow (earth)
Room Thermostat #1NWiring Centre2Blue (neutral)
DrawWarm CombiRTWiring Centre10Orange
Room Thermostat #1SLWiring Centre5Brown (live)
2-Port Valve (heating)EWiring Centre3Green/yellow (earth)
2-Port Valve (heating)NWiring Centre2Blue (neutral)
2-Port Valve (heating)BWiring Centre5Brown (live)
2-Port Valve (heating)GWiring Centre1Grey
2-Port Valve (heating)OWiring Centre10Orange
Room Thermostat #2LWiring Centre1Brown (live)
Room Thermostat #2NWiring Centre2Blue (neutral)
Room Thermostat #2SLWiring Centre9Brown (live)
2-Port Valve (second heating zone)BWiring Centre9Brown (live)
2-Port Valve (second heating zone)OWiring Centre10Orange
2-Port Valve (second heating zone)GWiring Centre1Grey
2-Port Valve (second heating zone)NWiring Centre2Blue (neutral)
2-Port Valve (second heating zone)EWiring Centre3Green/yellow (earth)

Where it connects

Back to every wiring diagram.

If this is your home: this page is written for heating engineers, and for learners under the supervision of one. It explains how the wiring works; it is not training to do the work. In England and Wales, electrical work in a home must meet the Building Regulations (Part P), and some of it must be notified to building control or done by a registered electrician; Scotland and Northern Ireland have their own rules. For the wiring, call a registered electrician or a heating engineer competent in controls. Work inside a gas boiler is for a Gas Safe registered engineer only. If you smell gas, leave the building and call the gas emergency number: 0800 111 999 in Great Britain, 0800 002 001 in Northern Ireland.