S-Plan · wiring diagram

S-Plan Plus wiring diagram

In short

An S-Plan is a fully pumped heating system with two 2-port motorised zone valves, one for central heating and one for hot water, driven by a programmer, a room thermostat and a cylinder thermostat. Each valve’s end switch feeds the boiler’s switched live, so the boiler fires only while a valve is open: the boiler interlock.

Two heating zones and hot water: three 2-port valves, and two room stats sharing the programmer's one heating channel, on DrawWarm's own heat-only boiler pumping through its own PUMP OUT. The second zone's call is on block 9. The wiring centre is fed from the boiler's 230 V OUT: one supply for the boiler and its controls.

S-Plan wired in the DrawWarm simulator

An S-Plan wired in the simulator; this page’s circuit is listed wire by wire below. Wire colours as the lessons teach them. The meter reads what the circuit is doing.

The wiring centre, block by block

A block is a plain conductor: every wire landed on it is joined to every other, and to nothing else. The numbers are the habit the DrawWarm Method teaches, so the next engineer can read your work.

BlockAs the lessons teach itWired here
1Permanent live from the fused spur, and both valves’ greysDrawWarm Heat Only OUT_L, 2-Port Valve (heating) G, 2-Port Valve (hot water) G, Dual Channel Programmer L, 2-Port Valve (second heating zone) G
2NeutralDrawWarm Heat Only OUT_N, Room Thermostat #1 N, 2-Port Valve (heating) N, 2-Port Valve (second heating zone) N, Room Thermostat #2 N, 2-Port Valve (hot water) N, Dual Channel Programmer N
3EarthDrawWarm Heat Only OUT_E, 2-Port Valve (heating) E, 2-Port Valve (second heating zone) E, 2-Port Valve (hot water) E, Dual Channel Programmer E
4Heating demand from the programmer, out to the room thermostatRoom Thermostat #1 L, Room Thermostat #2 L, Dual Channel Programmer 4
5The room thermostat’s call, out to the heating valve’s brownRoom Thermostat #1 SL, 2-Port Valve (heating) B
6Hot water demand from the programmer, out to the cylinder thermostatCylinder Thermostat C, Dual Channel Programmer 3
8The cylinder thermostat’s call, out to the hot water valve’s brown2-Port Valve (hot water) B, Cylinder Thermostat 1
9A second heating zone’s call, where there is one2-Port Valve (second heating zone) B, Room Thermostat #2 SL
10The valves’ oranges in, the boiler’s switched live outDrawWarm Heat Only SL, 2-Port Valve (heating) O, 2-Port Valve (second heating zone) O, 2-Port Valve (hot water) O

Every wire, terminal by terminal

FromTerminalToTerminalColour
Fused SpurEDrawWarm Heat OnlyEGreen/yellow (earth)
Fused SpurNDrawWarm Heat OnlyNBlue (neutral)
Fused SpurLDrawWarm Heat OnlyLBrown (live)
DrawWarm Heat OnlyPLCirculation PumpLBrown (live)
DrawWarm Heat OnlyPNCirculation PumpNBlue (neutral)
DrawWarm Heat OnlyPECirculation PumpEGreen/yellow (earth)
DrawWarm Heat OnlyOUT_LWiring Centre1Brown (live)
Room Thermostat #1LWiring Centre4Black
DrawWarm Heat OnlyOUT_NWiring Centre2Blue (neutral)
DrawWarm Heat OnlyOUT_EWiring Centre3Green/yellow (earth)
DrawWarm Heat OnlySLWiring Centre10Orange
Room Thermostat #1NWiring Centre2Blue (neutral)
Room Thermostat #1SLWiring Centre5Brown (live)
2-Port Valve (heating)EWiring Centre3Green/yellow (earth)
2-Port Valve (heating)NWiring Centre2Blue (neutral)
2-Port Valve (heating)BWiring Centre5Brown (live)
2-Port Valve (heating)GWiring Centre1Grey
2-Port Valve (heating)OWiring Centre10Orange
2-Port Valve (second heating zone)EWiring Centre3Green/yellow (earth)
2-Port Valve (second heating zone)NWiring Centre2Blue (neutral)
2-Port Valve (second heating zone)BWiring Centre9Brown (live)
2-Port Valve (second heating zone)OWiring Centre10Orange
2-Port Valve (hot water)BWiring Centre8Brown (live)
2-Port Valve (hot water)OWiring Centre10Orange
Cylinder Thermostat1Wiring Centre8Brown (live)
Cylinder ThermostatCWiring Centre6Grey
Room Thermostat #2SLWiring Centre9Brown (live)
Room Thermostat #2NWiring Centre2Blue (neutral)
Room Thermostat #2LWiring Centre4Black
Dual Channel Programmer4Wiring Centre4Black
Dual Channel Programmer3Wiring Centre6Grey
2-Port Valve (hot water)GWiring Centre1Grey
2-Port Valve (hot water)NWiring Centre2Blue (neutral)
2-Port Valve (hot water)EWiring Centre3Green/yellow (earth)
Dual Channel ProgrammerNWiring Centre2Blue (neutral)
Dual Channel ProgrammerLWiring Centre1Brown (live)
Dual Channel ProgrammerEWiring Centre3Green/yellow (earth)
2-Port Valve (second heating zone)GWiring Centre1Grey

Where it connects

Back to every wiring diagram.

If this is your home: this page is written for heating engineers, and for learners under the supervision of one. It explains how the wiring works; it is not training to do the work. In England and Wales, electrical work in a home must meet the Building Regulations (Part P), and some of it must be notified to building control or done by a registered electrician; Scotland and Northern Ireland have their own rules. For the wiring, call a registered electrician or a heating engineer competent in controls. Work inside a gas boiler is for a Gas Safe registered engineer only. If you smell gas, leave the building and call the gas emergency number: 0800 111 999 in Great Britain, 0800 002 001 in Northern Ireland.